π Batteries
Connecting a storage battery to Fuzz makes it possible to follow its state of charge and to control it: charge it with solar surplus, discharge it to limit the draw from the grid, or follow a grid exchange setpoint. This page covers the connection; the full form and the strategies are described in Add and control a battery.
β Prerequisitesβ
| Item | Required |
|---|---|
| Asset | A battery from the compatible list, using Modbus TCP, Modbus RTU or MQTT |
| Hosting mode | Modbus: Edge or Hybrid. MQTT: all modes |
| Role | Administrator or Operator of the site |
| Battery setting | Modbus enabled, and remote power control allowed in the battery management system (otherwise Fuzz can only measure it) |
π What Fuzz measures and controls on a batteryβ
Measurements: depending on the model, Fuzz reads the charge or discharge power, the current per phase, the state of charge (SoC, in %), the state of health (SoH) and the capacity. They appear in Assets (Batteries filter), in the Energy flow diagram of the site Overview page (BATTERY) and can trigger alerts (see Create and manage alert definitions).
Control: with the Set power action ticked (ticked by default at creation), Fuzz sends the battery a charge or discharge power setpoint. The setpoint follows the chosen strategy.
The strategies offered in Default Production strategy are Grid Exchange Target (default: the battery charges or discharges to hold the target grid exchange), Maximum Consumption (charges at maximum) and Maximum Production (discharges at maximum). Their detailed behaviour is in Add and control a battery.
Choosing the strategy according to the objective is explained in Control a battery according to an objective. If Set power is unticked, the battery is only measured.
π₯οΈ Declare the battery in the Consoleβ
The form has seven steps: Battery parameters, Strategy parameters, Battery protocol, Phase mapping, Console, Metrics, Monitoring. The fields specific to the connection:
| Field | Meaning | Default |
|---|---|---|
| Battery name | Name, unique on the site | β |
| Switchboard, Meter | Connection switchboard; dedicated meter only if the battery does not provide its own measurements | β |
| Maximum consumption current (A) | Maximum charge current per phase. The Console shows the matching power: current Γ 690 (16 A = 11.04 kW) | 16 |
| Maximum discharge current (A) | Maximum discharge current per phase | 16 |
| Total capacity (kWh) | Usable capacity of the battery | β |
| Maximum State of Charge (%) | Fuzz does not charge above this | 95 |
| High State of Charge (%) | "Well-charged battery" threshold | 80 |
| Low State of Charge (%) | "Low battery" threshold | 20 |
| Minimum State of Charge (%) | Fuzz does not discharge below this | 10 |
| Protocol | Modbus or Mqtt, then Model | Modbus |
| Supported actions | Set power | Ticked at creation |
Enter currents and state of charge thresholds that are compatible with the manufacturer's limits: Fuzz calculates its setpoints from these values, it does not know the internal limits of the battery. The Modbus configuration is detailed in Modbus assets.
π Check and troubleshoot a batteryβ
The battery must be Online in Assets, with a state of charge consistent with the manufacturer's display. On the battery page, the real-time measurements card shows the power and the state of charge.
| Symptom | Probable cause | Solution |
|---|---|---|
| Battery offline | Address, unit ID, Modbus disabled | See Common Modbus problems |
| The battery does not follow the strategy | Set power unticked, remote control not allowed in the battery, state of charge outside the limits | Tick the action; allow external control in the battery; check the SoC thresholds |
| Charge and discharge reversed | Sign convention of the model or wiring | Contact Fuzz support with the battery reference |